Guide for Selection of Low-voltage Power Cables

2 years ago 1673 0 News


Selection of low-voltage power cable

 

In the AC system, the rated voltage between phases of the conductor of the power cable shall not be lower than the voltage of the working line of the usual circuit. The low-voltage power cable should be insulated with cross linked polyethylene or polyvinyl chloride.

低壓電力電纜2.png

 

In general, YJV-0.6/1KV - is selected

 

Choosing according to the cable environment and equipment characteristics.

 

- Flame retardant power cable: ZR-YJV-0.6/1kV-

 

- Fire-resistant power cable: NH-YJV-0.6/1kV-

 

- Rubber sleeve power cable: YC-450/750V-

 

- Flame retardant rubber sleeve power cable: ZR-YC-450/750V-

 

Selection of low voltage power cable section

 

The section of low-voltage power cable can be divided into the following four types according to the technical method:

 

Method of temperature rise

 

The allowable carrying capacity of the cable under the long-term continuous rated load should not be lower than the maximum calculated current value of the electrical load to ensure that the allowable temperature rise range of the cable. If the section is weak, the allowable load is less than the load current, the temperature rise will exceed the allowable value, accelerate the aging of insulation materials, reduce the insulation degree of wire, affect the safety of electricity.

 

On the contrary, the cable section is larger, will increase the cost of the project, resulting in the waste of materials and funds. Take long-term working three-phase power equipment, such as water pumps, fans, etc., for example.

 

Firstly, the calculated load is determined. If there is a single device, the calculated load is the rated capacity; if there are several devices, the calculated load is the sum of all rated capacities and multiplied by the simultaneous use coefficient Ke, i.e., Pj=P, total Ke

低壓電力電纜.png

 

The calculation current is determined by calculating the load: Ij=Pj3Utah φ where Ue is the line voltage and COS φ is the power factor of the distribution system.

 

The traverse section is determined according to the cable laying mode and operating conditions, and the cable section is determined by querying the table and corresponding parameters in the table of "allowable current carrying capacity when 1~3KV cross linked polyethylene insulated cable is directly buried and laid".

 

Voltage loss method

 

When verifying the cross section according to voltage loss, all kinds of electrical equipment should be done to work normally and the terminal voltage when starting to meet the requirements.

 

Loss voltage: U= UE-UI

 

Where Ue is the rated voltage and Ui is the terminal voltage of the device.

 

Cable cross-sectional area: S=PjxL×△U%/C

 

Where S traverse section, unit mm2 : Pj is calculation capacity, unit kW: L is line length, unit m; U% is the percentage of voltage loss, generally 5%; C is the internal coefficient of the material, 77 for copper and 46.3 for aluminum.

 

Depending on the calculation results, according to the cable section series, select the wire.

 

The conductor shall meet the requirements of dynamic and thermal stability

 

When the low-voltage distribution line has a short-circuit fault, the conductor temperature will rise sharply due to the thermal effect of short-circuit current before the protection of electrical appliances, which will lead to the damage of conductor insulation.

 

According to the provision of Article 3.2.2 3 of the Code for Low-voltage Distribution Design (GB 50054-2011), the conductor section shall be selected, and the conductor shall meet the requirements of dynamic and thermal stability. The thermal stability of the insulated conductor shall be checked according to its cross-sectional area.

 

When the short circuit duration is less than or equal to 5S, the cross-sectional area of the insulated conductor must comply with the calculation formula of this specification. When the short circuit duration is less than 0.1s, the cross-sectional area of the insulated conductor should be regarded as the influence of the aperiodic component of the short circuit current. If the short circuit duration is longer than 5 seconds, the cross-sectional area of the insulation conductor must be accounted for the heat dissipation.

 

The minimum conductor section shall meet the requirements of mechanical strength

 

The lead wire should be enough to withstand normal tension and electric force, should not produce diameter reduction, fracture and other phenomena. In order to ensure the safe transmission of electric energy. The mechanical strength is closely related to the way of cable laying, such as multiple parallel laying in the air, underground directly buried laying, pipe laying, overhead laying, line groove playing, cable trench laying, cable tunnel laying, etc.

 

Different playing modes will affect the allowable carrying capacity of the wire. Mechanical damage caused by turning off power cables should also be paid attention to. During construction, if the turning Angle is too large, the conductor may be affected by mechanical damage, which may decrease the insulation degree of the cable and cause faults.

 

When the cable is turned or reserved, the cable should be naturally bent as much as possible to minimize the torsion force and internal mechanical damage.

 

In addition, in engineering practice, it is easy to ignore the temperature, blister, interference, corrosion and other adverse factors, which may lead to the occurrence of accidents or failure.

 

Economic current method

 

The so-called economic current is "the operating current corresponding to the applicable cross section that minimizes the sum of the investment and conductor loss cost during the life period". When selecting core section according to the technical method, only initial investment is generally considered.

 

When choosing the core section according to the current economic method, in addition to the initial investment of the computer, the conductor loss cost during the economic life period should also be considered, and the minimum sum of the two should be selected.

 

When the core section is reduced, the initial investment is reduced, but the line loss cost is increased. On the contrary, when the core section is increased, the line loss is decreased, but the initial investment is increased. And in a certain section of the range, the total cost is the least, this is our pursuit of the goal - efficient selection.

 

The total cost CT=CI+CJ, where CI is the sum of cable main material, accessory cost and construction cost, and CJ is the loss cost, which is related to load (current), cable resistance (section), annual operation time, electricity price, service life and other factors. Among them, it should be noted that:

 

When choosing core section, technology and economy are two aspects of one thing, interdependent and mutually restricted.

 

Because the core section of the cable is not continuous, the economic section and economic current have a definite range.

 

In the range of the economic section, can be selected by the smaller section.

 

The cable section of the spare circuit, such as the auxiliary motor circuit, should be selected according to half of the normal operating hours. For some circuits not used for a long time, it is not apt to choose the cross section according to the economic current.

 

According to the economic selection to determine the cable section, in order to ensure the reliability of electric power operation, but also can save energy, economically save costs, obtain the best economic benefits.

 

According to experience, choose the power cable, electrical design is often to determine the cable type according to installation conditions, and then according to the hot conditions to select the suitable for the current carrying capacity demands and meet the voltage loss and thermal stability of the cable, at the same time we should also check the voltage loss and mechanical strength, it is to use a more extensive way.

低壓電力電纜3.png

 

The cable section selected in this way is technically reliable. In line with large consumption of non-ferrous metal, it is advisable to select the cross section according to the economic current density in order to save non-ferrous metal and investment.

 

In theory, no matter choose according to what kind of method of cable section, should be according to the engineering condition, environmental characteristics, cable type and the number of factors, from the view of development, using other methods to check, according to a variety of methods to find the minimum cross-sectional area respectively, and then choose the maximum value as the final selected values, enables the cable selection to meet the requirements at the same time.

 

In this approach, the possibility of load development can be fully considered, and the voltage quality and work efficiency of electrical equipment can be improved, so as to prolong the service life of the cable.

Tags:
INQUIRY
主站蜘蛛池模板: 性日本少妇|无码粉嫩小泬无套在线观看|一级片九九|99国产精品久久久久久久成人|国产综合片|从大树开始的进化动漫免费观看 | 五月婷婷在线观看视频|国产熟女精品视频国语|97亚洲欧美国产网曝97|91中文精品|高潮迭起=av乳颜射后入|国产91精品久久久 | XXXX日本少妇做受|极品少妇videofreehd|日本无线免费视频|91免费视频|97久久精品人人做人人爽|亚洲一区二区三区四区在线播放 | 图片小说视频一区二区|国产我不卡|亚洲综合久久成人=a片|爱操视频|亚洲国产综合精品一区|欧美=aⅴ | 99免费看香蕉视频|久久伊人蜜桃=av一区二区|激情五月开心综合亚洲|国产午夜一级片|一级片的网站|一本精品99久久精品77 | 宅男噜噜噜66国产在线观看|色姑娘综合|99久久久国产精品日本久久区一|亚洲成人自拍网|国产亚洲精品第一综合另类|精品亚洲一 | 把女人弄爽=a片免费视频|999精品免费视频|五月婷在线|高清色惰WWW日本COM|一二三区=av|永久在线观看免费视频 | 国产精品国产精品国产专区不蜜|#NAME?|а∨天堂一区一本到|国产免费一区二区三区免费视频|国产又粗又硬又长又爽的视频|中文字幕无码第1页 | 天天干狠狠|欧美性受极品xxxx喷水|亚洲第2页|chinese乱子伦XXXXHD|色8久久精品久久久久久葡萄=av|青青草91在线视频 | 亚洲=aV综合=a国产=aV中文|亚洲涩88|久久99精品久久久久久狂牛|无遮挡h肉动漫在线观看|国产亚洲棕合欧美视频|中文字幕在线观 | 黄色网址免费在线观看|蜜臀=av夜夜澡人人爽人人桃色|极品少妇XXXXⅩ另类|国产成人一区二区无码不卡在线|亚洲无线视频|九九久久精品国产=aV片国产 | www.超碰在线.com|日本在线观看无码不卡V|免费观看日本污污ww网站|一区2区|91福利区|国产精品久久久久久238 | 在线观看免费黄网|久久久久久久久久久鸭|91社影院|日本一区免费网站|尹人香蕉久久99天天拍|任我爽橹在线精品视频 | 黄色一级短视频|啊片在线观看|91精品xxxx瑜伽裤日本|成人免费观看cn|亚洲熟妇色自偷自拍另类|免费=a观看 | 国产一区二区在线精品|久久久蜜桃=av|在线观看超碰|国内成人精品|髙清视频播放在线观看|中文国产字幕在线不卡 | 久久精品亚洲酒店|黄国产区|在线视频中文字幕|91精品欧美|三区中文字幕|日韩亚洲精品在线 | 图片小说视频一区二区|国产我不卡|亚洲综合久久成人=a片|爱操视频|亚洲国产综合精品一区|欧美=aⅴ | 亚洲精品无码成人=a片|国产美女口爆吞精普通话|国产精品国产三级国产专播i12|91精品国产一区自在线拍|日韩特级|成人在线免费观看小视频 | 狂躁美女大bbbbbb在线观看|亚洲=aV日韩=aV无码=a琪琪|BBW极度另类孕妇|中文资源在线官网|久久久久国产精品熟女影院|狠狠老司机 | 爱如潮水日本|宅男噜噜噜66网站高清|午夜宅男在线永久免费观看网|日日日干|国产成人精品一区二区三区无码|国产成人高清在线观看播放 | 黄色福利网站在线观看|亚洲深夜福利|免费的爱爱视频|成人国产免费观看|精品欧美一区二区久久|一区美女 | 国产成人=aⅴ|日韩一区二区福利视频|日韩在线视频看看|国产剧情一区|色猫咪=aV在线网址|一级免费在线 | 久久污视频|无码人妻精品中文字幕免费时间|日产无码精品一区二区三区|四虎最新免费网站|亚洲大尺度吃奶做爰|chinese叫床videos | 国产高跟丝袜脚交视频|最短的距离是圆的高清在线观看|一区二区三区视频播放|国产精品黄页在线播放免费|#NAME?|精品国产乱码久久久久久中文 | 丁香五月好婷婷深深爱|欧美、另类亚洲日本一区二区|www.com国产|免费观看又色又爽又湿的视频软件|国产一级生活片|一级黄色故事片 | 成人免费高清|精品色呦呦|国产另类ts人妖一区二区|99热精品在线|国产人免费人成免费视频|欧美国产日韩二区 | 国产精品视频最多的网站|韓國三級大全久久網站|日韩推理片免费观看|60岁老女人高潮表现|日本免费专区|亚洲第一成人在线观看 | 超碰在线进入|一级全黄少妇免费录像片|欧美大成色WWW永久网站婷|免费看=a=a=a=a=a级淫片涩爱=av|亚洲=av成人一区二区三区在线观看|99一级片 | c=aopom成人免费公开视频|中文字幕欧美人妻精品一区|91九幺丨成人|日韩久久国产|三年片大全免费观看|久草在在线 | 婷婷久久综合九色综合97最多收藏|国产一级毛片久久|91精品二区|思思99精品视频在线观看|国产福利第一视频在线播放|人人澡超碰碰 | 成人国产午夜在线观看|久久综合九色综合97欧美|99视频免费观看|久久久久久久国产精品毛片|久久99精品国产99久久|天堂成人国产精品一区 | 性欧美老人牲交xxxxx视频|成年人在线观看网址|日本黄色录像片|98婷婷狠狠成人免费视频|991久久|粉嫩欧美一区二区三区高清影视 | 日韩国产精品久久|黄=a在线|日韩视频久久|欧美亚洲日韩国产人成在线播放|超碰成人在线免费观看|欧美大屁股BBBBXXXX | 日本久久99成人网站|99视频在线免费看|亚洲一区成人在线观看|青草福利在线|中文字幕无线码中文字幕免费|亚洲视频h | 最近中文字幕在线mv视频在线|#NAME?|色惰网站|草逼一区|免费精品国产的网站免费观看|播放日韩一级黄色片 | 免费人妻无码=aV老色鬼|99爱影视|2018天天躁夜夜躁狠狠躁|#NAME?|91精品免费在线视频|国产免费二区 | 亚洲国产福利一区|免费无码午夜福利片69|99亚洲伊人久久精品影院红桃|日韩在线观看你懂的|在线观看99|91午夜国产 | 男女日批免费视频|九九免费观看全部免费视频|日韩精品免费一区二区夜夜嗨|中文字幕在线播放第一页|中国少妇xxxx|欧洲人体超大胆露私视频 | 大内密探零性|国产美女自拍小视频|久久久久久久综合狠狠综合|九九热免费精品|性=a毛片|午夜免费啪啪 | 亚洲乱小说|未满十八18禁止免费无码网站|日韩=av免费网址|在线国v免费看|人成午夜大片免费视频77777|亚洲激情影院 | 婷婷五月色中文字幕网|亚洲人成人77777网站|香蕉久久一区二区三区|亚洲成=a人片在线观看中|久久不见久久见免费影院视频|看黄在线观看 |